Toroidal Power Transformers


A toroidal transformer has ring type core made from cold rolled grain oriented ( CRGO ) Silicon steel strip without any joints and annealed for stress relief after being wound. These wound cores are then suitably insulated by class B insulation and the winding of copper wire is usually done by winding machines.
Toroidal Power Transformers
The core being continuous, without any air gap and the path of flux being along the direction of grain orientation, gives an opportunity for optimum use of flux density, besides very low iron loss and exciting current. The primary and secondary windings are closely linked magnetically. Therefore the leakage fluxes and reactance are negligible.

A toroidal transformer has its winding spread over the entire periphery of the core. This results in largcr area for dissipating the heat. Till recently all such small low voltage type transformers needs were met almost universally by traditional or conventional El transformers. Now materials are easily available, so it has been possible to develop 'LOW VOLTAGE TOROIDAL TRANSFORMER' giving a whole set of advantages and wide range of applications in place of conventional transformers.
Advantages Over Conventional Transformer ( EI Type )
CUSTOM DESIGN FOR THE SPACE AVAILABLE: Since cores are manufactured in our own factory, it is possible to make a core of any diameter and height.
REDUCED REACTANCE: Isolation between primary and secondary easily feasible with class B insulation which results in reduced reactance.
LOW PRICE: Production techniques and more efficient design leading to cost effectiveness.
REDUCED TEMPERATURE RISE: Winding spread over the entire periphery of the core. This result in a larger area for dissipating the heat.
SMALLER SIZE AND WEIGHT: When used with a centering washer and screw / bolt, it becomes 40 % lighter and smaller.
LOW STRAY FIELD: Approximately 85-90 % lower than conventional transformers.Since toroids have no air gaps, primaries and secondaries are wound uniformly around the entire core resulting in toroid emitting very low radiated magnetic field.
NO INHERENT HUM / VIBRATION AND LOW NOISE: In toroid there is no air gaps and loose sheets of steel or lamination to cause vibration. Further copper winding are done on the above core so it almost completely eliminates the hum and noise.
EASE OF MOUNTING : Easy mounting by centering washer or Resin center potting with through hole and screw /bolt, or using bracket or combination of bracket and studs.
NEGLIGIBLE ' NO LOAD LOSS ' AND EXCITATION: In applications where a circuit is in a "stand - by mode" for a long period, the potential Cost reduction for power can be significant. Approximately 85 % at no load and 35 % under load condition.
SUITABLE FOR HIGHER FREQUENCY SUPPLY SYSTEMS.
HIGHER EFFICIENCY: All windings are symmetrically spread over the entire round gapless core, which gives an opportunity for higher use of flux density and reduced winding resistance, thus it achieves a very high electrical efficiency.
MAGNETIC SHIELDING FEASIBLE
 
BETTER REGULATION
 
BETTER RELIABLITY

Technical Specification

POWER RATING
DIMENSION (MM.)
WEIGHT
( VA. )

Outer

Height

( KG. )
15
75
30
0.39
20
75
30
0.41
25
75
35
0.47
30
85
30
0.57
40
85
35
0.71
50
95
35
0.89
60
95
35
0.93
80
105
35
1.23
100
105
40
1.42
120
110
50
1.61
150
110
55
1.87
200
125
50
2.35
250
125
55
2.67
300
140
50
3.11
400
140
55
3.63
500
145
70
4.46
600
170
60
5.41
800
175
70
6.4
900
175
70
6.53
1000
175
75
7.14
1500
185
85
9.36
2000
210
85
12.1
3000
235
90
15.9
Due to constant attempt to improve the design and due to change in the quality of material available, the figures given above are for general guidance only and are subject to confirmation.
Applications

Medical equipment, Audio / Video products , Motor control equipment, Lighting , Stabilized power supplies , Microprocessor based units , Battery chargers, Telecommunication products , Instrumentation , Computer and peripherals , CNC controlled machines , CRT, Robot equipment, Industrial Control Equipments, Office machines etc.

By considering above advantages, TOROIDAL TRANSFORMER is the one to be used in place of the old conventional type transformer.
ADVICE NOTE :
Care must be taken when mounting a toroid to ensure that both ends of the fixing bolt must not be allowed to simultaneously come into contact with the metal chassis or framework, as this could act as a shorted turn.
 